TEL6-180
Valve Regulated Lead Acid Battery
for communications standby power applications

FEATURES

  • Flame-arresting one-way pressure-relief vent for safety and long life.
  • Thermally welded case-to-cover bond to ensure a leak-proof seal.
  • Flame-retardant polypropylene case and cover compliant with UL94 V-0 with an Oxygen Limiting Index of greater than 28.
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination 99% plus.
  • Thick positive plate design for maximum service float life – 10 year design life.
  • Complies with UL1778, 924, 1989 and 94 V-0.
  • UL-recognized component.
  • Can be used in any orientation. Upright, side or end mounting recommended.
  • Low-profile terminals with threaded copper alloy inserts for reduced height, reduced maintenance and increased safety.
  • Multicell design for ease of installation and maintenance.
  • Not restricted for air transport – Complies with IATA/ICAO Special Provision A67.
  • Not restricted for surface transport – classified as non-hazardous material as related to DOT-CFR Title 49 parts 171-189.
  • Not restricted for water transport – classified as non-hazardous material per IMDG Amendment 27.



*All dimension in inches and (millimeters). All dimensions are for reference only. Contact a C&D Representative for complete  dimensional information.

TEL6-180 - Specifications
Cells
Per Unit
Voltage
Per
Unit
Weight
Electrolyte
Maximum
Discharge Current
Short
Circuit Current
Ohms Imped.
60 Hz
3
6.42
72 lbs.
33 kg.
Absorbed H2SO4
SG= 1.300
800 Amps
4350 Amps
@ 0.1 sec.
0.0015 Ohms
Capacity
176 Ah @ 8 hour rate to 1.75 volts per cell @ 77° F (25° C)
171 Ah @ 10 hour rate to 1.80 volts per cell @ 20° C (68° F)
Operating Temperature Range
Discharge; -40° F ( -40° C to +160° F (71° C)
Charge; -10° F (-23° C) to +140° F (60° C)
(with temperature compensation)
Nominal Operating Temperature Range
+74° F (23°C) to +80° F (27° C)
Float Charging Voltage
6.75 to 6.9 VDC/unit Average @ 77° F (25° C)
Recommended Maximum Charging Current Limit
C/5 amperes (40 amps @ 100% depth of discharge)
Maximum AC Ripple (Charger)
0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Maximum voltage allowed = 4% P-P
Maximum current allowed =10 amperes RMS (C/20)
Self Discharge
Dynasty Telecom batteries may be stored for up to 6 months at 77°F (25° C) and then a freshening charge is required. For higher temperatures the time interval will be shorter.
Accessories
Inter unit connectors, racks and cabinet systems available.
Terminal
Threaded copper alloy insert terminal to accept 1/4-20 UNC bolt.
Terminal Hardware Initial Torque
110 in.-lbs. (12.4 N-m)

Note: Batteries to be mounted with 0.5 in. spacing minimum and free air ventilation. Specifications are subject to change without notification.

>> BACK <<