| TEL6-180 - Specifications |
| Cells Per Unit | Voltage Per Unit | Weight | Electrolyte | Maximum Discharge Current | Short Circuit Current | Ohms Imped. 60 Hz  |
| 3 | 6.42 | 72 lbs. 33 kg. | Absorbed H2SO4 SG= 1.300 | 800 Amps | 4350 Amps @ 0.1 sec. | 0.0015 Ohms |
| Capacity | 176 Ah @ 8 hour rate to 1.75 volts per cell @ 77° F (25° C) 171 Ah @ 10 hour rate to 1.80 volts per cell @ 20° C (68° F) |
| Operating Temperature Range | Discharge; -40° F ( -40° C to +160° F (71° C) | Charge; -10° F (-23° C) to +140° F (60° C) (with temperature compensation) |
| Nominal Operating Temperature Range | +74° F (23°C) to +80° F (27° C) |
| Float Charging Voltage | 6.75 to 6.9 VDC/unit Average @ 77° F (25° C) |
| Recommended Maximum Charging Current Limit | C/5 amperes (40 amps @ 100% depth of discharge) |
| Maximum AC Ripple (Charger) | 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Maximum voltage allowed = 4% P-P Maximum current allowed =10 amperes RMS (C/20) |
| Self Discharge | Dynasty Telecom batteries may be stored for up to 6 months at 77°F (25° C) and then a freshening charge is required. For higher temperatures the time interval will be shorter. |
| Accessories | Inter unit connectors, racks and cabinet systems available. |
| Terminal | Threaded copper alloy insert terminal to accept 1/4-20 UNC bolt. |
| Terminal Hardware Initial Torque | 110 in.-lbs. (12.4 N-m) |